Dark Light
,

ATEN 20-Port Intelligent 0U Power Distribution Unit (PDU), Metered by Bank (20 x C13) PE5220s


As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (PDUs) to effectively increase the efficiency of data center power usage. The NRGence PE5220s eco PDU is an intelligent PDU that contains 20 AC outlets and is available in various IEC or NEMA socket configurations. It provides the ability to monitor the center’s health environment via sensors*.

  • Connections
  • Support 10/100Mbit Ethernet Interface
  • Support TCP/IP, UDP, HTTP, HTTPS, SSL, DHCP, SMTP, NTP,DNS, Auto Sense, Ping, Telnet, and SNMP V1,V2&V3
  • Support 2-level account/password security, IP/MAC filter, 128 bit SSL, RADIUS
  • Support : eco Sensors, Browser ( IE, Firefox, Chrome, Safari )
  • Metering
  • Bank level power metering and monitoring
  • Environment Monitoring : support external temperature/temperature & humidity sensors for rack temperature and humidity monitoring
  • Current, voltage, power, power dissipation, temperature, and humidity metering and threshold level setting
  • Outlet Switch Control
  • Always On
SKU: ATE_PE5220s Categories: ,
Function PE5220sA PE5220sB PE5220sG
Electrical
Nominal Input Voltage 100 – 120 VAC 100 – 240 VAC 100 – 240 VAC
Maximum Input Current 20A Max; 16A(UL de-rated) 20A Max; 16A(UL de-rated) 16A Max
Input Frequency 50-60 Hz 50-60 Hz 50-60 Hz
Input Connection NEMA 5-20P NEMA 6-20P IEC 60320 C20
Input Power 2400 VA(Max); 1920 VA(UL de-rated) 4160 VA(Max); 3328 VA(UL de-rated) 3680 VA(Max)
Outlet Type Total: 20 x NEMA 5-15R Total: 20 x IEC320 C13 Total: 20 x IEC320 C13
Nominal Output Voltage 100 – 120 VAC 100 – 240 VAC 100 – 240 VAC
Maximum Output Current (Outlet) NEMA 5-15R: 15A(Max); 12A(UL de-rated) C13: 15A(Max); 12A(UL de-rated) C13: 10A(Max)
Maximum Output Current (Bank) 20A(Max); 16A(UL de-rated) 20A(Max); 16A(UL de-rated) 16A(Max)
Maximum Output Current (Total) 20A(Max); 16A(UL de-rated) 20A(Max); 16A(UL de-rated) 16A(Max)
Breakers 1 x 20A Non-Fuse breaker 1 x 20A Non-Fuse breaker 1 x 16A Non-Fuse breaker
Metering Bank level Current, Voltage, VA , PF and KWh Monitoring Bank level Current, Voltage, VA , PF and KWh Monitoring Bank level Current, Voltage, VA , PF and KWh Monitoring
Outlet Switching None None None
Environment Sensor Ports 2 2 2
Metering Accuracy Voltage Range: 100VAC ~ 250VAC +/-1%
Power Range: 100W ~ Maximum Capacity +/- 2%
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Voltage Range: 100VAC ~ 250VAC +/-1%
Power Range: 100W ~ Maximum Capacity +/- 2%
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Voltage Range: 100VAC ~ 250VAC +/-1%
Power Range: 100W ~ Maximum Capacity +/- 2%
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Physical Properties
Dimensions (L x W x H) 69.14 x 6.60 x 4.40 cm
(27.22 x 2.6 x 1.73 in.)
69.14 x 6.60 x 4.40 cm
(27.22 x 2.6 x 1.73 in.)
69.14 x 6.60 x 4.40 cm
(27.22 x 2.6 x 1.73 in.)
Weight 2.13 kg ( 4.69 lb ) 2.13 kg ( 4.69 lb ) 2.13 kg ( 4.69 lb )
Power Cord Length 3 m 3 m 3 m
Environmental
Operating Temperature 0–50°C 0–50°C 0–50°C UL 60950(EN 60950 de-rated 0°C–30°C)
Storage Temperature -20–60°C -20–60°C -20–60°C
Humidity (Operating & Storage) 0 – 80% RH, Non-Condensing 0 – 80% RH, Non-Condensing 0 – 80% RH, Non-Condensing
Compliance
EMC Verification FCC Part 15 Class A, Others by Request FCC Part 15 Class A, Others by Request CE, Others by Request
Safety Verification TUV-CB, Others by Request TUV-CB, Others by Request TUV-CB, CE-LVD, Others by Request