Dark Light
,

ATEN 20A/16A 16-Outlet Metered-Ready Energy PDU PE1216


• PE1216A: 100~120V; North America, Mexico, Japan, Taiwan
• PE1216B: 200~240V; North America, Mexico, Japan, Taiwan
• PE1216G: International

The PE1216 Energy PDU contains 16 AC outlets and is available in IEC or NEMA socket configurations. The PE1216 Energy PDU features a space-saving 0U design that allows it to be mounted vertically on the outside of a rack, resulting in a more efficient use of space in the server room, while providing 16 AC outlets.

  • Space saving 0U rack mount design
  • IEC or NEMA outlet models
  • Real-time PDU current monitoring *

    * When used in conjunction with the EC1000 Energy Box

SKU: ATE_PE1216 Categories: ,
Function PE1216A PE1216B PE1216G
Electrical
Nominal Input Voltage 100 – 120 VAC 100 – 240 VAC 100 – 240 VAC
Maximum Input Current 20A(Max) 20A(Max) 16A(Max)
Input Frequency 50-60 Hz 50-60 Hz 50-60 Hz
Input Connection NEMA 5-20P NEMA 6-20P IEC 60320 C20
Input Power 2400 VA(Max) 4160 VA(Max) 3680 VA(Max)
Outlet Type Total: 16 x NEMA 5-15R Total: 16 x IEC320 C13 Total: 16 x IEC320 C13
Nominal Output Voltage 100 – 120 VAC 100 – 240 VAC 100 – 240 VAC
Maximum Output Current (Outlet) 15A(Max) 15A(Max) 10A(Max)
Maximum Output Current (Bank) 20A(Max) 20A(Max) 16A(Max)
Maximum Output Current (Total) 20A(Max) 20A(Max) 16A(Max)
Breakers 1 x 20A Non-Fuse Breaker 1 x 20A Non-Fuse Breaker 1 x 16A Non-Fuse Breaker
Metering Bank Level Current Monitoring (Via EC1000 Energy Box) Bank Level Current Monitoring (Via EC1000 Energy Box) Bank Level Current Monitoring (Via EC1000 Energy Box)
Outlet Switching None None None
Environment Sensor Ports 0 0 0
Metering Accuracy Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Physical Properties
Dimensions (L x W x H) 73.00 x 4.40 x 4.40 cm
(28.74 x 1.73 x 1.73 in.)
73.00 x 4.40 x 4.40 cm
(28.74 x 1.73 x 1.73 in.)
73.00 x 4.40 x 4.40 cm
(28.74 x 1.73 x 1.73 in.)
Weight 1.32 kg ( 2.91 lb ) 1.32 kg ( 2.91 lb ) 1.32 kg ( 2.91 lb )
Power Cord Length 3 m 3 m 3 m
Environmental
Temperature (Operating / Storage) 0–50°C / -20–60°C 0–50°C / -20–60°C 0–50°C / -20–60°C
Humidity (Operating & Storage) 0–80% RH, Non-Condensing 0–80% RH, Non-Condensing 0–80% RH, Non-Condensing
Compliance
EMC Verification FCC, Others by Request FCC, Others by Request CE, C-Tick, Others by Request
Safety Verification cTUVus, PSE, Others by Request cTUVus, PSE, Others by Request TUV-CB, GOST, Others by Request