Dark Light
,

ATEN 28-Port Intelligent 0U Power Distribution Unit (PDU), Metered by Outlet (24 x C13, 4 x C19) PE7328


As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (eco PDUs) to effectively increase the efficiency of data center power usage. The NRGence PE7328 eco PDUs are intelligent PDUs that contain 28 AC outlets and are available in various IEC socket configurations.

NRGence eco PDUs provide secure, centralized, intelligent, power management (power on, off, cycle) of data center IT equipment (servers, storage systems, KVM switches, network devices, serial data devices, etc.), as well as the ability to monitor the center’s health environment via sensors.

  • Connections
  • Support 10/100Mbit Ethernet Interface
  • Support TCP/IP, UDP, HTTP, HTTPS, SSL, DHCP, SMTP, NTP, DNS, Auto Sense, Ping, SNMP V1,V2&V3
  • Support 2-level account/password security, IP/MAC filter, 128 bit SSL, RADIOUS
  • Support : eco Sensors, Browser ( IE, Firefox, Chrome, Safari )

  • Metering
  • PDU and outlet level power metering and monitoring
  • Environment monitoring — supports external temperature/temperature & humidity sensors for rack temperature and humidity monitoring
  • Current, voltage, power, power dissipation, temperature, and humidity metering and threshold level setting
  • Support door sensor

  • Outlet Switch Control
  • Always On
SKU: ATE_PE7328 Categories: ,
Function PE7328B PE7328G
Electrical
Nominal Input Voltage 100 – 240 VAC 100 – 240 VAC
Maximum Input Current 30A Max; 24A(UL de-rated) 32A Max
Input Frequency 50-60 Hz 50-60 Hz
Input Connection NEMA L6-30P IEC 60309 32A
Input Power 6240 VA(Max) 4992 VA (UL de-rated) 7360 VA(Max)
Outlet Type Total: 24 x IEC320 C13 + 4 x IEC320 C19
Bank1: Outlet 1 – 14; 12 x C13 + 2 x C19
Bank2: Outlet 15 – 28; 12 x C13 + 2 x C19
Total: 24 x IEC320 C13 + 4 x IEC320 C19
Bank1: Outlet 1 – 14; 12 x C13 + 2 x C19
Bank2: Outlet 15 – 28; 12 x C13 + 2 x C19
Nominal Output Voltage 100 – 240 VAC 100 – 240 VAC
Maximum Output Current (Outlet) C13: 15A (Max); 12A(UL de-rated)
C19: 15A (Max); 12A(UL de-rated)
C13: 10A(Max)
C19: 16A(Max); TUV De-rated 15A(Max)
Maximum Output Current (Bank) 15A(Max); 12A(UL de-rated) 16A(Max)
Maximum Output Current (Total) 30A(Max); 24A(UL de-rated) 32A(Max)
Breakers 2 x 16A UL489 Breaker 2 x 16A UL489 Breaker
Metering Outlet Level Current, Voltage, VA, PF, KWh Monitoring Outlet Level Current, Voltage, VA, PF, KWh Monitoring
Outlet Switching None None
Environment Sensor Ports 4 4
Metering Accuracy Voltage Range: 100VAC ~ 250VAC +/-1%
Power Range: 100W ~ Maximum Capacity +/- 2%
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Voltage Range: 100VAC ~ 250VAC +/-1%
Power Range: 100W ~ Maximum Capacity +/- 2%
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Physical Properties
Dimensions (L x W x H) 135.98 x 6.60 x 4.40 cm
(53.54 x 2.6 x 1.73 in.)
135.98 x 6.60 x 4.40 cm
(53.54 x 2.6 x 1.73 in.)
Weight 5.05 kg ( 11.12 lb ) 5.05 kg ( 11.12 lb )
Power Cord Length 1.6 m 1.6 m
Environmental
Temperature (Operating / Storage) 0 – 50°C / -20 – 60°C 0 – 40°C / -20 – 60°C
Humidity (Operating & Storage) 0 – 80% RH, Non-Condensing 0 – 80% RH, Non-Condensing
Compliance
EMC Verification FCC Part 15 Class A, Others by Request CE, Others by Request
Safety Verification By Request CE-LVD, Others by Request