ATEN Basic PDU Series PE0112


The PE0112 series Basic PDU contains 12 AC outlets and is available in IEC or NEMA socket configurations. The PE0112 series Basic PDU features a space-saving 1U design that allows it to be mounted vertically on the outside of a rack, resulting in a more effi cient use of space in the server room, while providing 12 AC outlets.

  • Basic PDU
    • Space saving -1U rack mount design
    • IEC or NEMA outlet models
    • Overcurrent Protection
    • Aluminum material
  • Typical Applications
    • Servers
    • Network Devices
    • Telecom Equipment
SKU: ATE_PE0112 Categories: ,
Function PE0112A PE0112G
Electrical
Nominal Input Voltage 100-120 VAC 100-240 VAC
Maximum Input Current 15A(Max)
(UL de-rated 12A Max)
(PSE 10A)
10A(Max)
Input Frequency 50-60 Hz 50-60 Hz
Input Connection NEMA 5-15P IEC-320 C14
Input Power 1800VA(MAX);
1440VA(UL de-rated)
2400 VA(Max)
Outlet Type (12) NEMA 5-15R (12) IEC 320 C13
Nominal Output Voltage 120 VAC 240V
Maximum Output Current (Outlet) 15A(Max)
(UL de-rated 12A Max)
(PSE 10A)
10A(Max)
Maximum Output Current (Bank) 15A(Max)
(UL de-rated 12A Max)
(PSE 10A)
10A(Max)
Maximum Output Current (Total) 15A(Max)
(UL de-rated 12A Max)
(PSE 10A)
10A(Max)
OPD(Overcurrent Protection Device) Yes Yes
Physical Properties
Dimensions (L x W x H) 48.80 x 4.40 x 4.50 cm
(19.21 x 1.73 x 1.77 in.)
48.80 x 4.40 x 4.50 cm
(19.21 x 1.73 x 1.77 in.)
Weight 0.62 kg ( 1.37 lb ) 0.62 kg ( 1.37 lb )
Power Cord Length 10ft(14#) 10ft(3×1.0mm2)
Environmental
Temperature (Operating / Storage) 0 – 40℃ / -20 – 60℃
*When the environmental temperature comes close 40 degrees, it is recommended to lower the load to 60% to comply to the safety regulations.
0 – 40℃ / -20 – 60℃
*When the environmental temperature comes close 40 degrees, it is recommended to lower the load to 60% to comply to the safety regulations.
Elevation (Operating / Storage) 3000m 3000m
Compliance
EMC Verification FCC Class A CE Class A
Safety Verification By Request CE,LVD