- Connections
- Support 10/100Mbit Ethernet Interface
- Support TCP/IP, UDP, HTTP, HTTPS, SSL, DHCP, SMTP, NTP, DNS, Auto Sense, Ping, Telnet, and SNMP V1,V2&V3
- Support 2-level account/password security, IP/MAC filter, 128 bit SSL, RADIOUS
- Support : eco DC, Browser ( IE, Firefox, Chrome, Safari )
- Metering
- PDU and outlet level power metering and monitoring
- Environment monitoring — supports external temperature/temperature & humidity sensors for rack temperature and humidity monitoring
- Current, voltage, power, power dissipation, temperature, and humidity metering and threshold level setting
- Support door sensor
- Outlet Switch Control
- Always On
Power Distribution & Rack Solutions, Rack PDU
ATEN 20A/16A 16-Outlet Outlet-Metered eco PDU PE7216
As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (eco PDUs) to effectively increase the efficiency of data center power usage. The NRGence PE7216 eco PDUs are intelligent PDUs that contain 16 AC outlets and are available in various IEC socket configurations.
NRGence eco PDUs provide secure, centralized, intelligent, power management of data center IT equipment (servers, storage systems, KVM switches, network devices, serial data devices, etc.), as well as the ability to monitor the center’s health environment via sensors.
Function | PE7216B | PE7216G |
Electrical | ||
Nominal Input Voltage | 100 – 240 VAC | 100 – 240 VAC |
Maximum Input Current | 20A Max; 16A(UL de-rated) | 16A Max |
Input Frequency | 50-60 Hz | 50-60 Hz |
Input Connection | NEMA 6-20P | IEC 60320 C20 |
Input Power | 4160 VA(Max); 3328 VA(UL de-rated) | 3680 VA(Max) |
Outlet Type | Total: 14 x IEC320 C13 + 2 x IEC320 C19 Bank1-1: Outlet 1 – 8; 7 x C13 + 1 x C19 Bank1-2: Outlet 9 – 16; 7 x C13 + 1 x C19 |
Total: 14 x IEC320 C13 + 2 x IEC320 C19 Bank1-1: Outlet 1 – 8; 7 x C13 + 1 x C19 Bank1-2: Outlet 9 – 16; 7 x C13 + 1 x C19 |
Nominal Output Voltage | 100 – 240 VAC | 100 – 240 VAC |
Maximum Output Current (Outlet) | C13: 15A (Max); 12A(UL de-rated) C19: 20A (Max); 16A(UL de-rated) |
C13: 10A (Max) C19: 16A (Max) |
Maximum Output Current (Bank) | 20A(Max); 16A(UL de-rated) | 16A(Max) |
Maximum Output Current (Total) | 20A(Max); 16A(UL de-rated) | 16A(Max) |
Breakers | 1 x 20A Non-Fuse breaker | 1 x 16A Non-Fuse breaker |
Metering | Outlet Level Current, Voltage, VA, PF, KWh Monitoring | Outlet Level Current, Voltage, VA, PF, KWh Monitoring |
Outlet Switching | None | None |
Environment Sensor Ports | 4 | 4 |
Metering Accuracy | Voltage Range: 100VAC ~ 250VAC +/-1% Power Range: 100W ~ Maximum Capacity +/- 2% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% |
Voltage Range: 100VAC ~ 250VAC +/-1% Power Range: 100W ~ Maximum Capacity +/- 2% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% |
Physical Properties | ||
Dimensions (L x W x H) | 132.48 x 6.60 x 4.40 cm (52.16 x 2.6 x 1.73 in.) |
132.48 x 6.60 x 4.40 cm (52.16 x 2.6 x 1.73 in.) |
Weight | 3.70 kg ( 8.15 lb ) | 3.70 kg ( 8.15 lb ) |
Power Cord Length | 1.6 m | 1.6 m |
Environmental | ||
Temperature (Operating / Storage) | 0 – 50°C / -20 – 60°C | 0 – 40°C / -20 – 60°C |
Humidity (Operating & Storage) | 0 – 80% RH, Non-Condensing | 0 – 80% RH, Non-Condensing |
Compliance | ||
EMC Verification | FCC Part 15 Class A, Others by Request | CE, Others by Request |
Safety Verification | TUV-CB, Others by Request | TUV-CB, CE-LVD, Others by Request |